C00137 | brake transistor utilisation, C00138 | brake resistor utilisation, C00142 | autom. restart after mains on – Lenze 9400 User Manual
Page 747: C00142, C00137, C00138, 14 parameter reference

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
747
14
Parameter reference
14.2
Parameter list | C00137
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00137
C00138
C00142
Parameter | Name:
C00137 | Brake transistor utilisation
Data type: INTEGER_32
Index: 24438
d
= 5F76
h
From software version V1.5
Display range
(min. value | unit | max. value)
0
%
250
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00138 | Brake resistor utilisation
Data type: INTEGER_32
Index: 24437
d
= 5F75
h
From software version V1.5
Display range
(min. value | unit | max. value)
0
%
250
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00142 | Autom. restart after mains ON
Data type: UNSIGNED_32
Index: 24433
d
= 5F71
h
Starting performance of the controller after mains connection and reset of "Trouble", "Fault" or "Safe torque off
active".
Danger!
• If automatic restart is enabled (
= "1: Enabled"), the drive can restart automatically from the "Trouble"
and "Safe torque off" device states when the trouble or request for "Safe torque off active" has been eliminated!
• The controller enable generated by the application via a connection of the terminal 28 (RFR) with one of the
digital outputs DIGOUT_bOut(x) is not permissible if the following functions are active:
"Auto-start after mains ON" (
= "1") and "Program auto-start after mains switching" (
= "1")
If this is not observed, the controller can start automatically after mains connection!
Automatic restart after mains connection
Selection list
(Lenze setting printed in bold)
0 Inhibited
1 Enabled
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1