C01199 | enhanced power, C01200 | dual motor temperature, C01201 | delay time for fan start – Lenze 9400 User Manual
Page 838: C01199, For cont, C01200/1, C01200/2, 14 parameter reference

14
Parameter reference
14.2
Parameter list | C01199
838
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01199
C01200
C01201
Parameter | Name:
C01199 | Enhanced Power
Data type: UNSIGNED_32
Index: 23376
d
= 5B50
h
From software version V3.0
Stop!
During operation with increased continuous power, the max. permissible ambient temperature is reduced to 40 °C.
The overload current must be reduced. An overload current of 180 % for 10 s is no longer permissible during
operation with increased continuous power.
Operation with increased continuous power
Selection list
(Lenze setting printed in bold)
0 Enhanced Power off
1 Enhanced Power Mode 1 on
2 Enhanced Power Mode 2 on
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C01200 | Dual motor temperature
Data type: INTEGER_32
Index: 23375
d
= 5B4F
h
From software version V7.0
Motor temperature monitoring of a second motor
Display range
(min. value | unit | max. value)
-200
°C
200
Subcodes
Info
C01200/1
Motor temperature via X7
C01200/2
Motor temperature via X8
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C01201 | Delay time for fan start
Data type: UNSIGNED_32
Index: 23374
d
= 5B4E
h
From software version V8.0
Selection list
(Lenze setting printed in bold)
0 Via power section serial no.
1 500 ms
2 1000 ms
3 1500 ms
4 2000 ms
5 2500 ms
6 3000 ms
7 3500 ms
8 4000 ms
9 4500 ms
10 5000 ms
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1