C00581 | resp. to external fault, C00582 | resp. to heatsink temp. > c00122, C00583 | resp. to motor kty overtemp – Lenze 9400 User Manual
Page 797: C00584 | resp. to motor temp. > c00121, C00581, C00584, T in, C00583, Is activated, Se set in

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
797
14
Parameter reference
14.2
Parameter list | C00581
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00581
C00582
C00583
C00584
Parameter | Name:
C00581 | Resp. to external fault
Data type: UNSIGNED_32
Index: 23994
d
= 5DBA
h
Response to an external error
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
3 Quick stop by trouble
4 Warning locked
5 Warning
6 Information
0 No response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00582 | Resp. to heatsink temp. > C00122
Data type: UNSIGNED_32
Index: 23993
d
= 5DB9
h
Response if heatsink temperature > variable limit temperature (
).
Selection list
(Lenze setting printed in bold)
1 Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00583 | Resp. to motor KTY overtemp.
Data type: UNSIGNED_32
Index: 23992
d
= 5DB8
h
Response if motor temperature > fixed limit temperature.
Selection list
(Lenze setting printed in bold)
1 Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00584 | Resp. to motor temp. > C00121
Data type: UNSIGNED_32
Index: 23991
d
= 5DB7
h
Response if motor temperature > variable limit temperature (
).
Selection list
(Lenze setting printed in bold)
1 Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1