Cpu: overtemperature [0x00770009, Heatsink: thermal detector is defect [0x0077000a, Motor: thermal detector is defect [0x0077000c – Lenze 9400 User Manual
Page 643: 0x00770009, 0x0077000a, 0x0077000b, 0x0077000c, 13 diagnostics & fault analysis

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
643
13
Diagnostics & fault analysis
13.7
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CPU: Overtemperature [0x00770009]
Heatsink: Thermal detector is defect [0x0077000a]
Inside the device: Thermal detector is defective [0x0077000b]
Motor: Thermal detector is defect [0x0077000c]
Module ID (decimal)
Error ID (decimal)
119: Temperature monitoring
9
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CPU temperature higher than fixed limit temperature
(85 °C).
• Ambient controller temperature too high.
• Dirty fan or ventilation slots.
• Check control cabinet temperature.
• Clean filter.
• Clean controller.
Module ID (decimal)
Error ID (decimal)
119: Temperature monitoring
10
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Encoder for heatsink temperature supplies undefined
values.
Check control cabinet temperature, maybe it is too low.
Module ID (decimal)
Error ID (decimal)
119: Temperature monitoring
11
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Encoder for interior temperature supplies undefined
values.
Check control cabinet temperature, maybe it is too low.
Module ID (decimal)
Error ID (decimal)
119: Temperature monitoring
12
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The signals of the connected encoder for the motor
temperature detection (resolver at X7 or encoder at X8)
are outside the defined operating range of the detection.
• Check contacts of the encoder cable at the motor and
controller.
• Check selection of the motor temperature sensor in
and make sure that it complies with the
assembly in the motor.
• Possibly switch off temperature sensor monitoring
(
="0").
• If a PTC is in the motor, activate the monitoring of the