Negative limit switch has triggered [0x00b80002, 0x00b80003, 0x00b80004 – Lenze 9400 User Manual
Page 698: 0x00b80002, 13 diagnostics & fault analysis

13
Diagnostics & fault analysis
13.7
Error messages of the operating system
698
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Negative limit switch has triggered [0x00b80002]
Motor brake: Angular drift with closed brake too high [0x00b80003]
Motor brake: Automatically activated after waiting time has elapsed [0x00b80004]
Module ID (decimal)
Error ID (decimal)
184: Basic drive functions
2
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
in negative traversing
direction has tripped.
Module ID (decimal)
Error ID (decimal)
184: Basic drive functions
3
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The stop position of the motor axis has changed by more
than the permissible angle of rotation set in
although the brake is engaged.
• Deactivate standstill monitoring (
= 0).
• Increase waiting time for status monitoring (
).
The standstill monitoring only starts after this
waiting time has elapsed.
• Increase brake closing time (
) since during the
brake closing time the standstill monitoring is not
active.
• Reduce threshold for brake activation (
).
Module ID (decimal)
Error ID (decimal)
184: Basic drive functions
4
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
This time monitoring will only be active if the speed
setpoint has reached the threshold for brake activation
(
).
If the actual speed value does not reach/fall below the
threshold set in
within the parameterised
waiting time for brake activation (
), the brake
will be closed due to time-out.
• Increase waiting time for brake activation (
).
• Reduce threshold for brake activation (
).