C00126
C00127
C00128
C00129
Parameter | Name:
C00126 | CPU temp. warning threshold
Data type: UNSIGNED_32
Index: 24449
d
= 5F81
h
Temperature threshold for advance warning of CPU temperature on the control card
• The response to reaching the threshold can be selected in
Setting range
(min. value | unit | max. value)
Lenze setting
0
°C
85 70 °C
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00127 | Mot. overload warning threshold
Data type: UNSIGNED_32
Index: 24448
d
= 5F80
h
Adjustable threshold for I
2
x t advance warning
• The advance warning is sent if the thermal motor load (
) is higher than the set threshold.
• The response to reaching the threshold can be selected in
Setting range
(min. value | unit | max. value)
Lenze setting
0
%
200 100 %
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00128 | Therm. motor time constant
Data type: UNSIGNED_32
Index: 24447
d
= 5F7F
h
Setting range
(min. value | unit | max. value)
0.1
min
600.0
Subcodes
Lenze setting
Info
C00128/1
1.0 min
Therm. time constant coil
C00128/2
5.0 min
Therm. time constant plates
Read access Write access CINH PLC STOP No transfer
Scaling factor: 10
Parameter | Name:
C00129 | Brake resistance value
Data type: INTEGER_32
Index: 24446
d
= 5F7E
h
Required for monitoring of the brake resistor temperature.
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
Ohm
500.0 180.0 Ohm
Read access Write access CINH PLC STOP No transfer
Scaling factor: 10