5
Motor interface
5.5
Sensorless vector control (SLVC)
164
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.5.1
Basic settings
After the motor and controller have been optimally adjusted to each other, the "initial
commissioning steps" described in the following table are sufficient for a quick initial
commissioning.
• Detailed information on the individual steps can be found in the following subchapters.
Tip!
A precise adjustment of the motor parameters for an improved concentricity factor and
stability is described in the chapter "
How to optimise the control behaviour and adjust it to the concrete application is described
Parameterisable additional functions are described correspondingly in the chapter
"
Parameterisable additional functions
Initial commissioning steps
1.
Parameterising speed and torque controller
2. Additional "flying restart" function:
• In the Lenze setting, this parameterisable additional function is activated.
• If the flying restart function is not required, deactivate this function.
Flying restart function ( 209)
Only deactivate the flying restart if it is ensured that the drive is always at standstill in the case of controller
enable!
3. Additional "DC-injection braking" function:
• In the Lenze setting, this parameterisable additional function is deactivated.
• If DC-injection braking is required, activate this function.