2 drive diagnostics with the »engineer, 13 diagnostics & fault analysis – Lenze 9400 User Manual
Page 600

13
Diagnostics & fault analysis
13.2
Drive diagnostics with the »Engineer«
600
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13.2
Drive diagnostics with the »Engineer«
When an online connection to the controller has been established, the connected controller can be
diagnosed and relevant actual controller states can be displayed in a clearly arranged visualisation
using the »Engineer«.
How to diagnose a drive with the »Engineer«:
1. Select the 9400 HighLine controller to be diagnosed in the Project view.
2. Click the
icon or select the OnlineGo online command to build up an online
connection with the controller.
3. Select the Diagnostics tab.
With an online connection, the Diagnostics tab displays current status information about the
controller:
Button
Function
Acknowledge error message (if the error cause has been eliminated).
Reading out logbook entries ( 605)
Display details of the current error.
Display all active sources of a controller inhibit.
Display all active sources of a quick stop.