3 "ls_digitalinput" system block, Ls_digitalinput" system block, 8i/o terminals – Lenze 9400 User Manual
Page 280: Control

8
I/O terminals
8.4
Digital inputs
280
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.4.3
"LS_DigitalInput" system block
The LS_DigitalInput system block displays the digital inputs and the status of the state bus in the
function block editor.
Output
DIS code | data type
Value/meaning
DIGIN_bCInh
| BOOL
Status signal "Controller inhibit"
• The control input RFR (X5/pin 9) for setting/deactivating controller inhibit is
fixedly connected to the device control (DCTRL) via an inverter.
TRUE Controller inhibit active
DIGIN_bIn1
| BOOL
...
DIGIN_bIn8
| BOOL
Digital input 1 ... 8
DIGIN_bStateBusIn
| BOOL
State bus status
"State bus" monitoring function ( 283)
TRUE A node connected to the state bus has set the state bus to LOW level
and the "Error" state has been set.
• The "Error" state is also set if a node connected to the state bus is
not supplied with voltage.
LS_DigitalInput
DIGIN_bIn1
DIGIN_bIn2
DIGIN_bIn5
DIGIN_bIn4
DIGIN_bIn3
X5
DIGIN_bIn6
DIGIN_bIn7
DIGIN_bIn8
DIGIN_bCInh
DIGIN_bStateBusIn
1
0
1
C00114/1...8
C00443/1...8
CONTROL
GI
RFR
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
GE
24E
SB
X2
DriveInterface
1