Diagnostics & fault analysis
13.7
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CAN module (MXI1): Faulty NMT master configuration [0x00a00020]
CAN module (MXI1) RPDO1: Telegram not received or faulty [0x00a10000]
CAN module (MXI1) RPDO2: Telegram not received or faulty [0x00a10001]
Module ID (decimal)
Error ID (decimal)
160: CAN module in MXI1: CAN-NMT master
32
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI1: A
configuration error has occurred in the network
management of the CAN master.
• Faulty download of an Engineer or PLC Designer
project.
• Invalid CAN master settings according to DS301V402
and DS405 in the Engineer or PLC Designer.
• Incorrect parameterisation of node guarding or
heartbeat.
• Repeat download
• Correct CAN settings in the project and regenerate
project.
Module ID (decimal)
Error ID (decimal)
161: CAN module in MXI1: CAN-PDO handler
0
Response (Lenze setting printed in bold)
Setting:
C13591/1
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI1: CAN-IN 1
error
• Incorrect PDO telegram length.
• Transmission error.
• Time monitoring of the PDOs has tripped.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate trouble in the environment (e. g. EMC).
• Select a different time monitoring or switch off time
monitoring.
Module ID (decimal)
Error ID (decimal)
161: CAN module in MXI1: CAN-PDO handler
1
Response (Lenze setting printed in bold)
Setting:
C13591/2
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI1: CAN-IN 2
error
• Incorrect PDO telegram length.
• Transmission error.
• Time monitoring of the PDOs has tripped.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate trouble in the environment (e. g. EMC).
• Select a different time monitoring or switch off time
monitoring.