3 process when brake is closed, 11 basic drive functions – Lenze 9400 User Manual
Page 543

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
543
11
Basic drive functions
11.12
Brake control
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.12.5.3 Process when brake is closed
The following process occurs if the enable of the requested basic function for traversing the drive is
deactivated again:
1. The drive is brought to standstill via the basic function "
", or, where required, also via the
basic function "
2. When speed setpoint and actual speed value have fallen below the speed threshold set in
:
• The output BRK_bReleaseBrakeOut is set to FALSE for closing the brake.
• The current torque is saved, so that, if necessary, it can be used for feedforward control
during the next start.
• Monitoring of the motor brake control module is deactivated temporarily.
• Monitoring of the status input is deactivated temporarily (if switched active via
• The elapse of the brake application time starts.
3. After the brake closing time has elapsed and the corresponding state change of the status
signal:
• The output BRK_bBrakeReleased is reset to FALSE.
• The controller inhibit is activated.
4. After the additional waiting time set for the status monitoring in
has elapsed:
• Monitoring of the motor brake control module is active again.
• Monitoring of the status input is active again (if switched active via
• Standstill monitoring is activated.