Mxi2: module has been changed [0x00680016, Memory module has been changed [0x00680017, Safety module has been changed [0x00680018 – Lenze 9400 User Manual
Page 629: Combination mxi1/mxi2 not possible [0x00680019, Firmware has been changed [0x0068001a, 0x00680019, 0x0068001a, 0x00680017, 0x00680016, 0x00680018

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
629
13
Diagnostics & fault analysis
13.7
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
MXI2: Module has been changed [0x00680016]
Memory module has been changed [0x00680017]
Safety module has been changed [0x00680018]
Combination MXI1/MXI2 not possible [0x00680019]
Firmware has been changed [0x0068001a]
Module ID (decimal)
Error ID (decimal)
104: Module identification
22
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The extension module in module slot MXI2 has been
changed since the last mains switching.
(Only information or warning locked if the hardware
type has also changed.)
Module ID (decimal)
Error ID (decimal)
104: Module identification
23
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The memory module has been changed since the last
mains switching.
(Only information or warning locked if the hardware
type has also changed.)
Module ID (decimal)
Error ID (decimal)
104: Module identification
24
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The safety module has been changed since the last
mains switching.
(Only information or warning locked if the hardware
type has also changed.)
Module ID (decimal)
Error ID (decimal)
104: Module identification
25
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Extension modules which are not supported in this
combination are plugged into module slots MXI1 &
MXI2.
Create permitted module combination.
Module ID (decimal)
Error ID (decimal)
104: Module identification
26
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The firmware of the operating system has been updated. - (Information only)