9 "trouble active" state, 10 "fault active" state, 11 "system fault active" state – Lenze 9400 User Manual
Page 103: Trouble active" state, Fault active" state, Trouble active, Fault active, System fault active, 4drive interface

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
103
4
Drive interface
4.3
Device states
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.3.9
"Trouble active" state
This device state becomes active as soon as a monitoring function responds for which the "Trouble"
error response has been parameterised.
• The motor has no torque (is coasting).
• The device state is automatically exited if the error cause is eliminated:
• "Trouble active" state < 500 ms: Return to the original device state.
• "Trouble active" state > 500 ms: Return via the device state "Safe torque off active".
4.3.10
"Fault active" state
This device state becomes active as soon as a monitoring function responds for which the "Fault"
error response has been parameterised.
4.3.11
"System fault active" state
This device status becomes active if a system fault occurs.
• The device state can only be exited by mains switching.
LED DRIVE READY
LED DRIVE ERROR
OFF
104: Trouble active
LED DRIVE READY
LED DRIVE ERROR
OFF
102: Fault active
LED DRIVE READY
LED DRIVE ERROR
OFF
20: System fault active