Internal error (file system lifetime) [0x0069000d, General error in the application [0x006a0000, Faulty program download [0x006a0001 – Lenze 9400 User Manual
Page 635: 0x006a0002, 0x006a0001, 0x006a0000, 0x0069000d, 13 diagnostics & fault analysis

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
635
13
Diagnostics & fault analysis
13.7
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Internal error (file system lifetime) [0x0069000d]
General error in the application [0x006a0000]
Faulty program download [0x006a0001]
Fault during the update of the inputs and outputs [0x006a0002]
Module ID (decimal)
Error ID (decimal)
105: Error check of the program memory during runtime
13
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The maximum number of permissible writing cycles has
been reached for the memory module.
Replace memory module, otherwise data may get lost.
Module ID (decimal)
Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs
0
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
General application error.
Mains switching. Transmit the application to the
controller again.
• Please contact Lenze if the problem occurs again.
Module ID (decimal)
Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs
1
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Faulty transmission of the application to the controller
(checksum error).
Repeat transmission.
Module ID (decimal)
Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs
2
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Internal error
Mains switching. Transmit the application to the
controller again.
• Please contact Lenze if the problem occurs again.