C02585 | brake control polarity, C02586 | starting torque 1, C02587 | starting torque 2 – Lenze 9400 User Manual
Page 863: C02588 | source of starting torque, C02589 | brake closing time, C02588, C02586, Is a, Ue 2, C02587

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
863
14
Parameter reference
14.2
Parameter list | C02585
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C02585
C02586
C02587
C02588
C02589
Parameter | Name:
C02585 | Brake control polarity
Data type: UNSIGNED_32
Index: 21990
d
= 55E6
h
Basic function "
Selection list
(Lenze setting printed in bold)
0 Not inverted
1 Inverted
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C02586 | Starting torque 1
Data type: INTEGER_32
Index: 21989
d
= 55E5
h
Basic function "
Setting range
(min. value | unit | max. value)
Lenze setting
-21474836.47
Nm
21474836.47 0.00 Nm
Read access Write access CINH PLC STOP No transfer
Scaling factor: 100
Parameter | Name:
C02587 | Starting torque 2
Data type: INTEGER_32
Index: 21988
d
= 55E4
h
Basic function "
Setting range
(min. value | unit | max. value)
Lenze setting
-21474836.47
Nm
21474836.47 0.00 Nm
Read access Write access CINH PLC STOP No transfer
Scaling factor: 100
Parameter | Name:
C02588 | Source of starting torque
Data type: UNSIGNED_32
Index: 21987
d
= 55E3
h
Basic function "
Selection list
(Lenze setting printed in bold)
0 Starting torque 1/2
1 Stopping value
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C02589 | Brake closing time
Data type: UNSIGNED_32
Index: 21986
d
= 55E2
h
Basic function "
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
60000 100 ms
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1