I-1016
Monitoring time for the nodes 1 ... 32 to be monitored via heartbeat.
• The parameterised time is rounded down to an integer multiple of 5 ms and must have a greater
value than the heartbeat producer time of the node to be monitored.
[9-18] Data telegram assignment
I-1017
Time interval for the transmission of the heartbeat telegram to one or several
consumers.
• The parameterised time is rounded down to an integer multiple of 5 ms.
• The heartbeat telegram is automatically sent as soon as a time > 0 ms is entered. In this case,
the "node guarding" monitoring function is deactivated.
• This object is related to the Lenze code
.
Index:
I-1016
Name:
Consumer heartbeat time
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
32
- (read access only)
ro
U32
1 ... 32: consumer heartbeat time
0
0
4294967295 rw
U32
Subindex
Meaning
Lenze code
0
Number of nodes to be monitored
1 ... 32
Node-ID and heartbeat time of the node 1 ... 32 to be
monitored
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31 ... bit 24
Bit 23 ... bit 16
Bit 15 ... bit 0
0
(reserved)
Node ID
Heartbeat time
in [ms]
Index:
I-1017
Name:
Producer heartbeat time
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Producer heartbeat time
0
0
ms
65535 rw
U32