I-1a00, 9"can on board" system bus – Lenze 9400 User Manual
Page 362

9
"CAN on board" system bus
9.10
Implemented CANopen objects | I-1A00
362
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-1A00
The object I-1A00 serves to send parameter data as TPDO1.
[9-28] Data telegram assignment
IEC 61131 process data words are mapped. Only whole bytes can be mapped (the granularity of the
mapping entries is one byte).
I-1A01
The object I-1A01 serves to send parameter data as TPDO2.
• For data telegram assignment, see object
Index:
I-1A00
Name:
TPDO1 mapping parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: number of mapped application
objects in PDO
0
0
8 rw
U8
1 ... 8: application object 1 ... 8
0
0
4294967295 rw
U32
Subindex
Meaning
0
Number of mapped objects
1 ... 8
Mapping entry 1 ... 8 for TPDO1
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31 ... bit 16
Bit 15 ... bit 8
Bit 7 ... bit 0
Index
Subindex
Length
Index:
I-1A01
Name:
TPDO2 mapping parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: number of mapped application
objects in PDO
0
0
8 rw
U8
1 ... 8: application object 1 ... 8
0
0
4294967295 rw
U32
Subindex
Meaning
0
Number of mapped objects
1 ... 8
Mapping entries 1 ... 8 for RPDO2