File projectselection.dat defect [0x008c0000, 0x00870008, 0x00890000 – Lenze 9400 User Manual
Page 669: 0x00880000, 0x008c0000, 13 diagnostics & fault analysis

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
669
13
Diagnostics & fault analysis
13.7
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CAN on board PDO manager: Faulty configuration [0x00870008]
CAN on board SDO server: Faulty configuration [0x00880000]
CAN on board SDO client: Faulty configuration [0x00890000]
File ProjectSelection.dat defect [0x008c0000]
Module ID (decimal)
Error ID (decimal)
135: "CAN on board": CAN-PDO handler
8
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CAN on board: CAN-PDO configuration error
• Faulty project download.
• Invalid CAN settings according to DS301V402 in the
Engineer or PLC Designer.
• Mapping variables have incorrect CANopen indices
according to DS405.
• Repeat download.
• Correct CAN settings in the project and regenerate
project.
Module ID (decimal)
Error ID (decimal)
136: "CAN on board": CAN-SDO server
0
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CAN on board: A configuration error has occurred in the
CAN SDO server.
• Faulty project download.
• Invalid SDO server settings according to DS301V402
in the Engineer or PLC Designer.
• Repeat download.
• Correct CAN settings in the project and regenerate
project.
Module ID (decimal)
Error ID (decimal)
137: "CAN on board": CAN-SDO client
0
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CAN on board: A configuration error has occurred in the
CAN SDO client.
• Faulty project download.
• Invalid SDO client settings according to DS301V402 in
the Engineer or PLC Designer.
• Repeat download
• Correct CAN settings in the project and regenerate
project.
Module ID (decimal)
Error ID (decimal)
140: Application project manager
0
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Internal error
Reformat memory module (
project download.