Plc configuration invalid [0x00b80000, Positive limit switch has triggered [0x00b80001, 0x00b20000 – Lenze 9400 User Manual
Page 697: 0x00b10000, 0x00b80000, 0x00b80001, 13 diagnostics & fault analysis

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
697
13
Diagnostics & fault analysis
13.7
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CAN module (MXI2) SDO server: Faulty configuration [0x00b10000]
CAN module (MXI2) SDO client: Faulty configuration [0x00b20000]
PLC configuration invalid [0x00b80000]
Positive limit switch has triggered [0x00b80001]
Module ID (decimal)
Error ID (decimal)
177: CAN module in MXI2: CAN-SDO server
0
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: In the CAN
SDO server a configuration error has occurred.
• Faulty project download.
• Invalid SDO server settings according to DS301V402
in the Engineer or PLC Designer.
• Repeat download.
• Correct CAN settings in the project and regenerate
project.
Module ID (decimal)
Error ID (decimal)
178: CAN module in MXI2: CAN-SDO client
0
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: In the CAN
SDO client a configuration error has occurred.
• Faulty project download.
• Invalid SDO client settings according to DS301V402 in
the Engineer or PLC Designer.
• Repeat download
• Correct CAN settings in the project and regenerate
project.
Module ID (decimal)
Error ID (decimal)
184: Basic drive functions
0
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
An invalid control configuration has occurred.
Load a different application.
Module ID (decimal)
Error ID (decimal)
184: Basic drive functions
1
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
in positive traversing
direction has tripped.