5motor interface – Lenze 9400 User Manual
Page 208

5
Motor interface
5.8
Parameterisable additional functions
208
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Example: Voltage increase in the DC bus when field weakening is switched off
(For instance by an active setting of the controller inhibit or by tripping a fault or error at high motor
speed.)
[5-31] Example: Possible DC-bus voltage > 800 V if field weakening gets lost
Field weakening
Speed n
Motor voltage peak value
Switched off
4000 rpm
560 V
5700 rpm
800 V
6000 rpm
840 V
Switched-on
6000 rpm
560 V
• If pulse inhibit is set at 6000 rpm and switched-on field
weakening, the DC bus is charged to over 800 V ().
• A speed limitation to 5700 rpm is required, as this speed
generates a DC-bus voltage of 800 V when the field
weakening mode is switched off.
n
U
4000
840 V
560 V
6000
> 800 V