11 basic drive functions – Lenze 9400 User Manual
Page 478

11
Basic drive functions
11.7
Positioning
478
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
POS_bInTarget
| BOOL
Status signal "Setpoint has reached target position"
FALSE Positioning is still active or has been aborted.
TRUE The current position setpoint has reached the target position.
POS_bActPosInTarget
| BOOL
Status signal "Actual position in the target"
• In case of sequence profiles: the target position of the last profile to be traversed.
Actual value-based evaluation "Target position reached" ( 480)
FALSE Positioning is still active or has been aborted.
TRUE The current actual position value of the drive has reached the target
of the last profile to be traversed within the tolerance window set in
POS_bDriveInTarget
| BOOL
From V5.0
Status signal "Drive in the target"
• In case of sequence profiles: the target position of the last profile to be traversed.
• The status is also output if the basic function "Positioning" is deactivated.
Actual value- and setpoint-based evaluation "Drive in the target" ( 481)
FALSE Positioning is still active or has been aborted.
FALSETRUE The current actual position value of the drive has reached the target
position within the profile to be traversed last within the tolerance
window set in
. At this time, the current position setpoint has
already reached the target position.
• In the case of positioning processes with sequence profiles, the
output is only set to TRUE after the last profile to be traversed.
TRUEFALSE The current actual position value of the drive has exited the
tolerance and hysteresis window set in
again
after a positioning process has been completed.
FALSETRUE
(once again)
= "1", a modulo evaluation is carried out in all cycles (Lenze
setting):
• The output is set to TRUE again if the current actual position value
of the drive enters the tolerance and hysteresis window in an
optional modulo cycle again.
If
= "0", a modulo evaluation is only carried out in the
modulo cycle of the target setpoint:
• The output is set to TRUE again if the current actual position value
of the drive enters the tolerance and hysteresis window in the
same modulo cycle again.
POS_dnSetPos_p
| DINT
Current position setpoint in [increments]
• Reference point is the home position.
POS_dnProfileTarget_p
| DINT
Target position of the current profile in [increments]
• Reference point is the home position.
POS_dnProfileSpeed_s
| DINT
Current setpoint speed of the current profile as speed in [rpm]
• Taking a speed override into consideration.
POS_
dwActualProfileNumber
| DWORD
Profile number (1 .... 100) of the current profile
Identifier
DIS code | data type
Value/meaning