Device output power
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.6
Device output power
The parameters described in the following subchapters influence the output power of the
controller.
4.6.1
Switching frequency
The controller uses a pulse-width modulation to generate its output voltage. The switching
frequency is used to change the control factor of the pulse-width modulation.
Automatic switching frequency reduction
In the Lenze setting, the "variable" switching frequency "8 kHz" has been selected in
, which
means that the controller automatically reduces the switching frequency depending on the
setpoint current.
• Depending on the current amount, it is changed down to an assigned switching frequency.
• The switching thresholds are device-dependent (see 9400 hardware manual, chapter "Rated
data").
• If a fixed switching frequency is selected in
instead of a variable one, there is no
switching frequency changeover, however, (due to the field frequency range 0...5 Hz) it can only
be traversed at a low continuous current and low maximum currents (see 9400 hardware
manual, chapter "Rated data").
Tip!
If a load profile and a fixed setting of the switching frequency (e. g. 8 kHz fixed) are given,
an I x t disconnection due to a high device utilisation can be avoided by selecting the
variable setting for the same switching frequency instead.
Note!
If parameterisation is carried out offline or if the memory module is exchanged between
different 9400 HighLine device types, always check the setting of the switching
frequency in
C00018
and adapt it, if required, to prevent a parameter error after the
parameter set download or module change!
The maximum output frequency of the controller is limited to 1/8 of the switching
frequency selected in
! (See the following table.)
Switching frequency (
1 kHz
2 kHz
4 kHz
8 kHz
16 kHz
Maximum output frequency:
125 Hz
250 Hz
500 Hz
1000 Hz
1999 Hz
Motor - number of pole pairs:
Maximum speed [rpm]
1
7500
15000
30000
60000
120000
2
3750
7500
15000
30000
60000
3
2500
5000
10000
20000
40000
4
1875
3750
7500
15000
30000
5
1500
3000
6000
12000
24000
6
1250
2500
5000
10000
20000