2 writing parameters, 9"can on board" system bus – Lenze 9400 User Manual
Page 323

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
323
9
"CAN on board" system bus
9.7
Parameter data transfer
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.7.3.2
Writing parameters
Task: The rated current of the connected motor with I
rated
= 10.2 A (code
) is to be entered in
the controller.
Telegram to drive
Response message from drive (if data have been correctly transmitted)
Identifier
User data
1st byte
2nd byte 3rd byte
4th byte
5th byte
6th byte
7th byte
8th byte
Command
Index
Subindex
Data 1
Data 2
Data 3
Data 4
0x0602
0x23
0xA7
0x5F
0x00
0x66
0x00
0x00
0x00
Explanations on the telegram to the drive
Identifier
= 1536 + node address = 1536 + 2 = 1538 = 0x0602
(1536 = SDO1 basic identifier to the controller)
Command
= 0x23 = "Write request" (request to write a parameter to the controller)
Index
= 24575 - code number = 24575 - 88 = 24487 = 0x5FA7
Subindex
= 0 (code
does not have any subcodes)
Data 1 ... 4
= 10,2 x 10 = 102 = 0x00000066
(Value for motor current, data type U32; display factor 1/10)
Identifier
User data
1st byte
2nd byte 3rd byte
4th byte
5th byte
6th byte
7th byte
8th byte
Command
Index
Subindex
Data 1
Data 2
Data 3
Data 4
0x0582
0x60
0xA7
0x5F
0x00
0x00
0x00
0x00
0x00
Explanations on the telegram from the drive
Identifier
= 1408 + node address = 1408 + 2 = 1410 = 0x0582
(1408 = SDO1 basic identifier from the controller)
Command
= 0x60 = "Write response" (acknowledgement of the write access from the controller)
Index
as in telegram to the drive
Subindex