C00577 | field weakening controller gain, C00578 | field weak. contr. reset time, C00579 | resp. to speed monitoring – Lenze 9400 User Manual
Page 796: C00580 | resp. to encoder open circuit, C00577, Time, C00578, Should remain set to, C00580, C00579

14
Parameter reference
14.2
Parameter list | C00577
796
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00577
C00578
C00579
C00580
Parameter | Name:
C00577 | Field weakening controller gain
Data type: UNSIGNED_32
Index: 23998
d
= 5DBE
h
At "0" the P component is deactivated, a pure I-controller is used.
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
Vs/V
2147483.647 0.000 Vs/V
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1000
Parameter | Name:
C00578 | Field weak. contr. reset time
Data type: UNSIGNED_32
Index: 23997
d
= 5DBD
h
At "240000.0 ms" the I component of the field weakening controller is deactivated.
Setting range
(min. value | unit | max. value)
Lenze setting
1.0
ms
240000.0 2000.0 ms
Read access Write access CINH PLC STOP No transfer
Scaling factor: 10
Parameter | Name:
C00579 | Resp. to speed monitoring
Data type: UNSIGNED_32
Index: 23996
d
= 5DBC
h
Response to activation of speed monitoring
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
5 Warning
4 Warning locked
3 Quick stop by trouble
0 No response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00580 | Resp. to encoder open circuit
Data type: UNSIGNED_32
Index: 23995
d
= 5DBB
h
Response to open circuit in encoder
Danger!
If the encoder is used as motor encoder:
In the event of an error, a safe operation of the motor cannot be ensured anymore!
For safety reasons, the "Fault" response should always be set for this case!
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
5 Warning
4 Warning locked
3 Quick stop by trouble
13 Quick Stop open loop by trouble
0 No response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1