Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
355
9
"CAN on board" system bus
9.10
Implemented CANopen objects | I-1400
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-1400
Communication parameter for receiving process data via RPDO1
[9-25] Data telegram assignment
How to change the identifier:
1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").
Index:
I-1400
Name:
RPDO1 communication parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
5
- (read access only)
ro
U8
1: COB-ID used by RPDO
0x200 + node ID
0
4294967295 rw
U32
2: transmission type
254
0
255 rw
U8
3: inhibit time
-
- (not used for RPDOs)
rw
U16
4: compatibility entry
-
- (reserved, read or write access leads to error message
0x06090011)
rw
U8
5: event timer
-
- (not used for RPDOs)
rw
U16
Subindex
Meaning
Lenze code
1
RPDO1 identifier
• The basic setting is according to the "Predefined
Connection Set": Identifier = 0x200 + node ID
2
RPDO Transmission type according to DS301 V4.02
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31
Bit 30
Bit 29 ... bit 11
Bit 10 ... bit 0
0/1
0/1
Extended identifier*
11-bit identifier
* The extended identifier is not supported. Bit 11 ... bit 29 must be set to "0".
Bit
Setting
Bit 30
0 RTR to this PDO possible (cannot be set).
1 RTR to this PDO not possible (Lenze).
Bit 31
0 PDO active
1 PDO inactive