C00173 | mains voltage, C00173, C00174 – Lenze 9400 User Manual
Page 753: Also affects the permi, C00134, 14 parameter reference

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
753
14
Parameter reference
14.2
Parameter list | C00173
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00173
Parameter | Name:
C00173 | Mains voltage
Data type: UNSIGNED_8
Index: 24402
d
= 5F52
h
Adjustment of the DC bus voltage thresholds
• Check during commissioning and adapt, if necessary.
• All drive components connected via the DC bus must have the same thresholds.
• For selection 0 ... 3, the undervoltage threshold is firmly defined depending on the device type (see "Rated data"
chapter in the Hardware Manual).
Note: Altering this setting also has an impact on the permissible device utilisation!
In the chapter "Rated data" of the hardware manual the device types and their permissible device utilisation at a
certain mains voltage and switching frequency are specified.
Selection list
(Lenze setting printed in bold)
Info
0 230 V
Operation on 230 V mains
• Threshold for "Undervoltage on" = 200 V
• Threshold for "Undervoltage off" = 225 V
• Overvoltage threshold = 400 V
• Brake chopper threshold = 390 V
1 400/415 V
Operation on 400 V mains/415 V mains
• Threshold for "Undervoltage on" = 285 V (BF1 to BF7)
• Threshold for "Undervoltage on" = 400 V (BF8 to BF10)
• Threshold for "Undervoltage off" = 430 V
• Overvoltage threshold = 800 V
• Brake chopper threshold = 725 V
2 460/480 V
Operation on 460 V mains/480 V mains
• Threshold for "Undervoltage on" = 490 V
• Threshold for "Undervoltage off" = 535 V
• Overvoltage threshold = 800 V
• Brake chopper threshold = 765 V
3 500 V
Operation on 500 V mains
• Threshold for "Undervoltage on" = 540 V
• Threshold for "Undervoltage off" = 585 V
• Overvoltage threshold = 800 V
• Brake chopper threshold = 790 V
4 230 V, LU configurable
Operation on 230 V mains
• Undervoltage threshold is defined in
.
• Overvoltage threshold = 400 V
• Brake chopper threshold = 390 V
5 400/415 V, LU configurable
Operation on 400 V mains/415 V mains
• Undervoltage threshold is defined in
.
• Overvoltage threshold = 800 V
• Brake chopper threshold = 725 V
6 460/480 V, LU configurable
Operation on 460 V mains/480 V mains
• Undervoltage threshold is defined in
.
• Overvoltage threshold = 800 V
• Brake chopper threshold = 765 V
7 500 V, LU configurable
Operation on 500 V mains
• Undervoltage threshold is defined in
.
• Overvoltage threshold = 800 V
• Brake chopper threshold = 790 V
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1