Parameter reference
14.2
Parameter list | C00008
734
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00008
C00011
C00018
C00019
Parameter | Name:
C00008 | Progress of device command
Data type: UNSIGNED_32
Index: 24567
d
= 5FF7
h
From software version V7.0
Display range
(min. value | unit | max. value)
0
4294967295
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00011 | Motor reference speed
Data type: UNSIGNED_32
Index: 24564
d
= 5FF4
h
For parameter setting via interface: In case of bigger changes, only change the setting in one step when the
controller is inhibited!
Setting range
(min. value | unit | max. value)
Lenze setting
50
rpm
50000 3000 rpm
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00018 | Switching frequency
Data type: UNSIGNED_32
Index: 24557
d
= 5FED
h
Selection list
(Lenze setting printed in bold)
Info
2 1 kHz fixed/drive-optimised
Note:
• The maximum output frequency of the controller is
limited to 1/8 of the switching frequency selected
here!
• The switching frequencies that can be selected
depend on the device type (see Hardware Manual,
chapter "Rated data").
• In the case of an offline parameter setting or when
exchanging the memory module between different
Servo Drives 9400 HighLine device types, always
check the setting of this parameter and adapt it, if
required, to prevent a parameter error after the
parameter set download or module change!
3 2 kHz fixed/drive-optimised
4 4 kHz fixed/drive-optimised
5 8 kHz fixed/drive-optimised
8 2 kHz var./drive-optimised
9 4 kHz var./drive-optimised
10 8 kHz var./drive-optimised
11 16 kHz var./drive-optimised
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00019 | Threshold - standstill recognition
Data type: UNSIGNED_32
Index: 24556
d
= 5FEC
h
Setting range
(min. value | unit | max. value)
Lenze setting
0
rpm
450 5 rpm
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1