C01120 | sync source, C01121 | sync cycle time, C01121 – Lenze 9400 User Manual
Page 832: C01120, Ed in, Time, Lected in, 14 parameter reference

14
Parameter reference
14.2
Parameter list | C01120
832
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01120
C01121
Parameter | Name:
C01120 | Sync source
Data type: UNSIGNED_8
Index: 23455
d
= 5B9F
h
Selection of the source for the synchronisation signals.
• The drive can only be synchronised by one source.
Note:
Set the selection "2: CAN module" for the communication module CANopen (E94AYCCA).
"CAN on board" system bus: sync telegram
Selection list
(Lenze setting printed in bold)
0 Off
1 CAN on-board
2 CAN module
4 Module in MXI1
5 Module in MXI2
6 Digital input 1
7 Digital input 2
8 Digital input 3
9 Digital input 4
10 Digital input 5
11 Digital input 6
12 Digital input 7
13 Digital input 8
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C01121 | Sync cycle time
Data type: UNSIGNED_32
Index: 23454
d
= 5B9E
h
Time interval at which the phase control loop (PLL) in the controller expects the synchronisation signals.
• The time interval set must correspond to the cycle of the synchronisation source.
Note: For synchronisation via the system bus (CANopen), only integer multiples of 1000 μs should be set.
Example: For the system bus, the interval between two synchronisation signals is set to 2 ms. If the system bus is to
be used as the synchronisation source, a synchronisation cycle of 2000 μs must be set in C01121.
"CAN on board" system bus: sync telegram
Setting range
(min. value | unit | max. value)
Lenze setting
250
μs
20000 1000 μs
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1