C00321 | can rpdox identifier, C00322 | can tpdox tx mode, C00321/1 – Lenze 9400 User Manual
Page 767: C00321/2, C00321/3, C00321/4, C00321, C00322/1, C00322/2, C00322/3

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
767
14
Parameter reference
14.2
Parameter list | C00321
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00321
C00322
Parameter | Name:
C00321 | CAN RPDOx identifier
Data type: BITFIELD_32
Index: 24254
d
= 5EBE
h
Identifier for RPDO1 ... RPDO4
• If bit 31 is set (0x8nnnnnnn), the RPDO is deactivated.
• The basic setting is according to the "Predefined Connection Set".
• Mapping of the CANopen objects
...
(see DS301 V4.02).
Setting range
0x00000000
0xFFFFFFFF
Value is bit-coded:
Info
Bit 0 COB-ID bit 0
• Bit 0 ... 10: COB-ID
• Bit 11 ... 30: Reserved
• Bit 31: PDO invalid
... ...
Bit 31 PDO invalid
Subcodes
Lenze setting
Info
C00321/1
0x00000201
RPDO1 identifier
• After a node address change and CAN reset node, the
value 0x200 + node address will be set by default.
C00321/2
0x00000301
RPDO2 identifier
• After a node address change and CAN reset node, the
value 0x300 + node address will be set by default.
C00321/3
0x00000401
RPDO3 identifier
• After a node address change and CAN reset node, the
value 0x400 + node address will be set by default.
C00321/4
0x00000501
Identifier RPDO4
• After a node address change and CAN reset node, the
value 0x500 + node address will be set by default.
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00322 | CAN TPDOx Tx mode
Data type: UNSIGNED_8
Index: 24253
d
= 5EBD
h
TPDO transmission type according to DS301 V4.02
• Types 0 (acyclic sync), 1-240 (cyclic sync), 254 (event-controlled manufacturer-specific), 255 (event-controlled
device-profile-specific) are supported.
• The basic PDO setting is "254" (event-controlled).
• Mapping of the CANopen objects
...
(see DS301 V4.02).
Setting range
(min. value | unit | max. value)
0
255
Subcodes
Lenze setting
Info
C00322/1
254
Transmission mode for TPDO1 ... TPDO4
C00322/...
C00322/4
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1