C00585
C00586
C00587
Parameter | Name:
C00585 | Resp. to motor overtemp. PTC
Data type: UNSIGNED_32
Index: 23990
d
= 5DB6
h
Response if motor temperature across PTC input T1/T2 too high.
Selection list
(Lenze setting printed in bold)
1 Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00586 | Resp. to resolver open circuit
Data type: UNSIGNED_32
Index: 23989
d
= 5DB5
h
Response to open circuit in resolver
Danger!
If the resolver is used as motor encoder:
In the event of an error, a safe operation of the motor cannot be ensured anymore!
For safety reasons, the "Fault" response should always be set for this case!
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
5 Warning
4 Warning locked
3 Quick stop by trouble
13 Quick Stop open loop by trouble
0 No response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00587 | Fan control status
Data type: BITFIELD_8
Index: 23988
d
= 5DB4
h
Display area
0x00
0xFF
Value is bit-coded:
Bit 0 Heatsink fan ON
Bit 1 Integral fan ON
Bit 2 Heatsink fan status 1
Bit 3 Heatsink fan status 2
Bit 4 Integral fan status
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1