Read error service register [0x00720000, External error [0x00750000, 0x20750000 – Lenze 9400 User Manual
Page 640: 0x006f0000, 0x00750000, 0x00720000, 0x006a001b, 13 diagnostics & fault analysis

13
Diagnostics & fault analysis
13.7
Error messages of the operating system
640
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Watchdog cycle is greater than task cycle [0x006a001b]
Control card: Supply voltage (24 V DC) too low [0x006f0000]
Read error service register [0x00720000]
External error [0x00750000]
Module ID (decimal)
Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs
27
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
An application has been downloaded
• with the highest priority task having a smaller cycle
than the parameterised watchdog cycle
or
• with the watchdog of the highest priority task being
deactivated.
You can acknowledge the error if you follow the below
procedure:
1. Activate watchdog
2. Set a watchdog cycle that is smaller than or equal to
the task cycle
3. Recreate the application and download it again
•
From software version V11.0:
If the device boots with
an application without an activated watchdog or with
a watchdog set incorrectly, only an information is
entered in the logbook.
Module ID (decimal)
Error ID (decimal)
111: Monitoring of the 24V supply voltage
0
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
External 24 V supply voltage of the control card is lower
than 18 V.
Check external supply voltage.
• If the external supply voltage is available and the
error message does not disappear, please contact
Lenze.
Module ID (decimal)
Error ID (decimal)
114: Service register
0
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
During reading or writing the service register a fault has
occurred.
Mains switching
• Please contact Lenze if the problem occurs again.
Module ID (decimal)
Error ID (decimal)
117: Device control
0
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The drive interface has activated the error message
"External error".
• The input DI_bSetExternError of the system block
LS_DriveInterface has been set to TRUE.
• Check external device to be monitored.
• Check assignment of the input DI_bSetExternError in
the application.