Code refresh [0x00690000, Internal error (memory area - logbook) [0x00690001, Internal error (lds instance data) [0x00690002 – Lenze 9400 User Manual
Page 632: 0x00690000, 0x00690002, 0x00690001, 0x00680024, 13 diagnostics & fault analysis

13
Diagnostics & fault analysis
13.7
Error messages of the operating system
632
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Real-time clock: Battery empty, time lost [0x00680024]
Code refresh [0x00690000]
Internal error (memory area - logbook) [0x00690001]
Internal error (LDS instance data) [0x00690002]
Module ID (decimal)
Error ID (decimal)
104: Module identification
36
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The battery integrated in the clock in the MM440
memory module is empty. The clock has been reset to its
initial value (01.01.1970 - 00:00:00 o'clock).
• If the memory module is used for the first time,
restart the controller to initialise the memory
module.
• If the problem occurs again, replace the memory
module.
Module ID (decimal)
Error ID (decimal)
105: Error check of the program memory during runtime
0
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Serious device error or component failure.
Switch the controller off and then on again.
• Please contact Lenze if the problem occurs again.
Module ID (decimal)
Error ID (decimal)
105: Error check of the program memory during runtime
1
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Serious device error or component failure.
Switch the controller off and then on again.
• Please contact Lenze if the problem occurs again.
Module ID (decimal)
Error ID (decimal)
105: Error check of the program memory during runtime
2
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Serious device error or component failure.
Switch the controller off and then on again.
• Please contact Lenze if the problem occurs again.