I-1029, I-1018, 9"can on board" system bus – Lenze 9400 User Manual
Page 349

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
349
9
"CAN on board" system bus
9.10
Implemented CANopen objects | I-1018
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-1018
I-1029
This object serves to set the communication status to which the controller is to change after a bus
off, a node/life guarding event or a heartbeat event.
Index:
I-1018
Name:
Identity object
Subindex
Default setting
Display range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
see below
0
4294967295 ro
U32
1: Vendor ID
2: Product code
3: Revision number
4: Serial number
Subindex
Meaning
1
Manufacturer's identification number
• The identification number allocated to Lenze by the organisation "CAN in
Automation e. V." is "0x0000003B".
2
Product code
0x94001 9400 StateLine
0x94002 9400 HighLine / ServoPLC
0x94004 9400 regenerative power supply module
3
Main and subversion of firmware
4
Serial number
Index:
I-1029
Name:
Error behaviour
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
1
- (read access only)
ro
U8
1: Communication error
0
0
2 rw
U8
Subindex
Meaning
Lenze code
1
Status change after bus off, node/life guarding event or
heartbeat event:
0 State change from "Operational" to "Pre-
operational"
1 No state change
2 State change to "Stopped"