9
"CAN on board" system bus
9.6
Process data transfer
306
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.6
Process data transfer
[9-6]
PDO data transfer from / to the higher-level host system
For the transfer of process data, four separated process data channels (PDO1 ... PDO4) are available.
Definitions
• Process data telegrams between the host system and the devices are distinguished in terms of
direction as follows:
• Process data telegrams to the device (RPDO)
• Process data telegrams from the device (TPDO)
• The CANopen process data objects are designated as seen from the node's view:
• Receive PDOs (RPDOx): Process data object received by a node
• Transmit PDOs (TPDOx): Process data object sent by a node
Note!
Data can only be exchanged via process data objects if the status is "Operational"!
Communication phases/network management