C00909
C00950
C00951
Parameter | Name:
C00909 | Speed limitation
Data type: INTEGER_16
Index: 23666
d
= 5C72
h
Speed limitation for speed setpoint
• For the upper speed limit value only positive values are permissible (0.0 % ... 175.0 %).
• For the lower speed limit value only negative values are permissible (-175.0 % ... 0.0 %).
Setting range
(min. value | unit | max. value)
-175.0
%
175.0
Subcodes
Lenze setting
Info
C00909/1
175.0 %
Upper speed limit value
C00909/2
-175.0 %
Lower speed limit value
Read access Write access CINH PLC STOP No transfer
Scaling factor: 10
Parameter | Name:
C00950 | VFC: V/f characteristic shape
Data type: UNSIGNED_32
Index: 23625
d
= 5C49
h
From software version V3.0
Selection list
(Lenze setting printed in bold)
0 Linear (V/f)
1 Quadratic (V/f²)
2 Curve
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00951 | VFC: V/f base frequency
Data type: INTEGER_32
Index: 23624
d
= 5C48
h
From software version V3.0
Setting range
(min. value | unit | max. value)
Lenze setting
1
Hz
5000 50 Hz
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1