4 optimising phase controller, Optimising phase controller, 5motor interface – Lenze 9400 User Manual
Page 153

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
153
5
Motor interface
5.4
Servo control (SC)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.4.1.4
Optimising phase controller
How to optimise the phase controller setting by means of the ramp response:
1. Run a typical speed profile and record the ramp response of the phase controller with the
• Motor control variables to be recorded:
Speed.dnSpeedSetpoint (speed setpoint)
Speed.dnActualMotorSpeed (actual speed value)
Speed.dnOutputPosCtrl (phase controller output)
Position.dnEncounteringError (following error)
2. Adjust the gain Vp of the phase controller under
and repeat oscilloscope recording
until the intended following error behaviour is reached and the motor runs sufficiently
smoothly during the constant travel phase.
3. Save parameter set (
= "11: Save start parameters").