I-1011, 9"can on board" system bus – Lenze 9400 User Manual
Page 346

9
"CAN on board" system bus
9.10
Implemented CANopen objects | I-1011
346
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-1011
Load Lenze setting.
• Corresponds to the device command
= "0: Load Lenze setting".
• This command serves to reset the parameters of the active application to the Lenze setting
which is stored in the firmware.
Read subindex 1
[9-15] Assignment of the data telegram (read )
Write subindex 1
In addition to the index and subindex, the telegram data must include the "load" signature (ASCII
characters; ISO 8859) so that the Lenze setting can be loaded.
• A response according to the DS301 V4.02 specification occurs while writing with a wrong
identifier.
[9-16] Assignment of the data telegram (write)
Index:
I-1011
Name:
Restore default parameters
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: highest subindex supported
1
- (read access only)
ro
U32
1: restore all default parameters
-
0
4294967295 rw
U32
Subindex
Meaning
Read
Write
0
Max. supported subindex: 1
-
(a write attempt triggers the error
message 0x06010002.)
1
Loading of all parameters possible.
Load Lenze setting.
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31 ... bit 1
Bit 0
0
0/1
Bit
Setting
Bit 0
0 Parameters cannot be loaded.
1 Parameters can be loaded (Lenze).
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
"d" = 0x64
"a" = 0x61
"o" = 0x6F
"l" = 0x6C