PDO mapping (MXI2): Faulty configuration [0x006a0016]
Fault in the control configuration [0x006a0017]
Retain memory of the application faulty [0x006a001a]
Module ID (decimal)
Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs
22
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: Incorrectly
configured process data mapping.
• The corresponding PDO channel is not installed, e. g.
because no communication module was selected for
module slot MXI2 in the Engineer project.
• The communication module selected for module slot
MXI2 in the Engineer project does not support PDO
mapping.
• The mapping information downloaded to the
controller is faulty.
• Integrate suitable communication module for
module slot MXI2 in the Engineer project.
• Check the configuration of the network. Then
recompile the project and transmit it to the controller.
Module ID (decimal)
Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs
23
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
An invalid control configuration has occurred.
Load a different application.
Module ID (decimal)
Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs
26
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
During reading or saving the retain memory of the
application a fault has occurred.
Check whether the memory module suitable for the
application is plugged in.
Mains switching.
(
) = 33 (reset program).
Carry out project download again.
• Please contact Lenze if the problem occurs again.