4.7.2
Monitoring of external events
Use the input DI_bSetExternError of the
system block to monitor external events
by means of corresponding logic operations and activate the error message "External error" in the
controller.
Parameterising a response to an external error
The controller response to the error message "External error" can be selected under
Activation of "External error" error message
The error message "External error" is activated by setting the input DI_bSetExternError to TRUE.
• After this, the error number for the error message "External error" "
" (when "Fault"
has been selected as response) will be stored in the internal fault memory (
).
Reset error message
The error message "External error" and other active error messages are reset by setting the input
DI_bResetError to TRUE.
• If the input DI_bSetExternError is still set to TRUE, the reset will not be carried out.
• Error messages can only be reset if the cause of the error has been eliminated.