Page 357: 9"can on board" system bus

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
357
9
"CAN on board" system bus
9.10
Implemented CANopen objects | I-1403
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-1403
Communication parameter for the reception of process data via RPDO4
• For assignment of the data telegram see object
I-1600
The object I-1600 serves to receive parameter data as RPDO1.
[9-26] Data telegram assignment
IEC 61131 process data words are mapped. Only whole bytes can be mapped (the granularity of the
mapping entries is one byte).
Index:
I-1403
Name:
RPDO4 communication parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
5
- (read access only)
ro
U8
1: COB-ID used by RPDO
0x500 + node ID
0
4294967295 rw
U32
2: transmission type
254
0
255 rw
U8
3: inhibit time
-
- (not used for RPDOs)
rw
U16
4: compatibility entry
-
- (reserved, read or write access leads to error message
0x06090011)
rw
U8
5: event timer
-
- (not used for RPDOs)
rw
U16
Subindex
Meaning
Lenze code
1
Identifier RPDO4
• The basic setting is according to the "Predefined
Connection Set": Identifier = 0x500 + node ID
2
RPDO Transmission type according to DS301 V4.02
Index:
I-1600
Name:
RPDO1 mapping parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: number of mapped application
objects in PDO
0
0
8 rw
U8
1 ... 8: application object 1 ... 8
0
0
4294967295 rw
U32
Subindex
Meaning
0
Number of mapped objects
1 ... 8
Mapping entries 1 ... 8 for RPDO1
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31 ... bit 16
Bit 15 ... bit 8
Bit 7 ... bit 0
Index
Subindex
Length