Parameter | Name:
C00597 | Resp. to motor phase failure
Data type: UNSIGNED_32
Index: 23978
d
= 5DAA
h
Response to activation of motor phase failure monitoring
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
5 Warning
4 Warning locked
3 Quick stop by trouble
0 No response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00598 | Resp. to open circuit AIN1
Data type: UNSIGNED_32
Index: 23977
d
= 5DA9
h
Response if with master current at AIN1 and "LifeZero" mode (±4...±20mA) the current is in the non-permitted range
(-4 ... +4 mA).
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
3 Quick stop by trouble
4 Warning locked
5 Warning
6 Information
0 No response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00599 | Motor phase failure threshold
Data type: INTEGER_32
Index: 23976
d
= 5DA8
h
Current value for activating the
Motor phase failure monitoring
• In [%] relating to the maximum device current (display in
).
• The response to be triggered by the monitoring can be selected in
Setting range
(min. value | unit | max. value)
Lenze setting
1.0
%
100.0 5.0 %
Read access Write access CINH PLC STOP No transfer
Scaling factor: 10
Parameter | Name:
C00600 | Resp. to DC bus overvoltage
Data type: UNSIGNED_32
Index: 23975
d
= 5DA7
h
Response to DC bus overvoltage
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1