3 activate/deactivate quick stop, 11 basic drive functions – Lenze 9400 User Manual
Page 391

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
391
11
Basic drive functions
11.3
Quick stop
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.3.3
Activate/deactivate quick stop
For activation/deactivation of quick stop by the application, the three inputs QSP_bActivate1...3 are
provided.
• The three control inputs are linked via a logic OR gate, i.e. in order to activate quick stop, only
one of the three inputs must be set to TRUE. To deactivate quick stop, though, all three inputs
must be reset to FALSE.
• The control inputs can be linked with terminals (digital inputs) and/or process data in the
function block editor.
Further options for activating quick stop
• Via device command "Activate quick stop" (
= "45"), e.g. via a corresponding SDO of a
higher-level control, an HMI or »Engineer«.
• Via the key at the keypad, unless the Lenze setting of
(assignment of the key) has
been changed.
• Through the response "quick stop by trouble" parameterised for monitoring.
Note!
In the standard technology applications the control input QSP_bActivate1 is linked with
the digital input DI1 in the Lenze setting.