C01081 | l_dfrfg_1: sync. direction / tp function, C01082 | ls_writeparamlist: execute mode, C01083 | ls_writeparamlist: error status – Lenze 8400 User Manual
Page 981: C01083, Displays an, C01082, 16 parameter reference

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
981
16
Parameter reference
16.2
Parameter list | C01081
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01081
C01082
C01083
Parameter | Name:
C01081 | L_DFRFG_1: Sync. direction / TP function
Data type: UNSIGNED_8
Index: 23494
d
= 5BC6
h
From version 12.00.00
Selection list
1 cw/ccw - without TP
2 cw - without TP
3 ccw - without TP
4 cw/ccw - with TP
5 cw - with TP
6 ccw - with TP
Subcodes
Lenze setting
Info
C01081/1
1: cw/ccw - without TP
: Sync. direction / TP function
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C01082 | LS_WriteParamList: Execute Mode
Data type: UNSIGNED_8
Index: 23493
d
= 5BC5
h
: Selection of the activation method
Selection list
(Lenze setting printed in bold)
Info
0 by Execute
The writing of the parameter list is activated by a
FALSE/TRUE edge at the bExecute input.
1 by Input Select
The writing of the parameter list is carried out if a change
is made at the select inputs and if the controller is
initialised.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C01083 | LS_WriteParamList: Error status
Data type: UNSIGNED_16
Index: 23492
d
= 5BC4
h
: Error status:
• 0 = no error
• 33803 | 0x840B = invalid data type (e.g. STRING)
• 33804 | 0x840C = limit violation
• 33806 | 0x840E = invalid code
• 33813 | 0x8415 = no element of the selection list
• 33815 | 0x8417 = writing of the parameter not permitted
• 33816 | 0x8418 = writing of the parameter only permitted if controller is inhibited
• 33829 | 0x8425 = invalid subcode
• 33865 | 0x8449 = no parameter with subcodes
Display range
(min. value | unit | max. value)
0
34000
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1