Oc6: i2xt motor overload, Oc6: i2xt overload motor, Error message – Lenze 8400 User Manual
Page 597: Lp1: motor phase failure, Xx.0123.00099, Xx.0123.00145, Xx.0123.00105, Xx.0123.00098, Xx.0123.00200, 9diagnostics & error management

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
597
9
Diagnostics & error management
9.10
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
oC16: Torque controller limitation [xx.0123.00098]
FC03: Field controller limitation [xx.0123.00099]
oC6: I2xt overload - motor [xx.0123.00105]
LP1: Motor phase failure [xx.0123.00145]
Sd10: Speed limit - feedback system 12 [xx.0123.00200]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Actuator limitation according to speed controller.
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The output of the field controller has reached its
maximum limit value. The drive is at the torque limit in
the field weakening range.
• Observe load requirements.
• Correct dimensioning or reduce setpoint from the
field weakening range if necessary.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Thermal overload of the motor.
Only self-ventilated motors can be monitored using the
I2xt function.
• Check whether is it a self-ventilated motor. If not, set
to "0: No Reaction".
• Observe load requirements.
• Correct dimensioning if necessary.
• For VFCplus control type: Check Vmin boost (
).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Motor phase failure - power section
• This error message is displayed if a motor phase
carries less current of one half-wave than set in
.
• Check the motor connections and the corresponding
plug connector on the device and, if necessary, the
motor terminal box.
• Check the trigger threshold (
).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Maximally permissible speed of the feedback system
connected to DI1/DI2 reached.
Reduce speed of the rotation shaft/feedback system.
n
encoder
<= (f
max
x 60) / encoder increment
(for f
max
= 10 kHz)