Function library
18.1
Function blocks | L_NSet_1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Definition of the blocking zones
The subcodes of codes
and
can be used to define three zones which are to be
skipped by the output setpoint and which are to be passed as fast as possible by the ramp function
generator.
The example below shows the parameter setting of two blocking zones:
[18-46] Zone masking by means of parameterisable blocking zones
• The parameterised blocking zones have the same effect on negative input signals.
• A blocking zone is deactivated by entering identical limit values (in our example: Blocking zone
3).
Parameter
Blocking zone 1
Blocking zone 2
Blocking zone 3
Minimum limit value
C00633/1: 48 %
C00633/2: 138 %
C00633/3: 0 %
Maximum limit value
C00632/1: 104 %
C00632/2: 178 %
C00632/3: 0 %
Blocking zone 1
Blocking zone 2
Output [%]
Input [%]
1
0
199.99
-199.99
-199.99
199.99
C00632/1
C00633/1
48
138
0
1
104
178
C00632/2
C00633/2