C00607 | resp. to max freq. feedb. dig12/56, C00608 | resp. to maximum torque, C00609 | resp. to maximum current – Lenze 8400 User Manual
Page 857: C00609, C00608, Onse set in, C00607, 16 parameter reference

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
857
16
Parameter reference
16.2
Parameter list | C00607
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00607
C00608
C00609
C00610
C00611
C00612
Parameter | Name:
C00607 | Resp. to max freq. feedb. DIG12/56
Data type: UNSIGNED_8
Index: 23968
d
= 5DA0
h
Response when the maximum input frequency has been reached via the digital inputs.
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00608 | Resp. to maximum torque
Data type: UNSIGNED_8
Index: 23967
d
= 5D9F
h
Response if the maximum torque (
) is reached.
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00609 | Resp. to maximum current
Data type: UNSIGNED_8
Index: 23966
d
= 5D9E
h
Response if the maximum current (
) is reached.
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00610 | 16-bit connection table
Data type: UNSIGNED_16
Index: 23965
d
= 5D9D
h
This code is for device-internal use only and must not be written to by the user!
Parameter | Name:
C00611 | Bool connection table
Data type: UNSIGNED_16
Index: 23964
d
= 5D9C
h
This code is for device-internal use only and must not be written to by the user!
Parameter | Name:
C00612 | 32-bit connection table
Data type: UNSIGNED_16
Index: 23963
d
= 5D9B
h
This code is for device-internal use only and must not be written to by the user!