C00597 | resp. to motor phase failure, C00598 | resp. to i/o monitoring, C00599 | motor phase failure threshold – Lenze 8400 User Manual
Page 855: C00597, C00599, Will take place, N error response is set in, C00598, C00598/1, C00598/2

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
855
16
Parameter reference
16.2
Parameter list | C00597
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00597
C00598
C00599
Parameter | Name:
C00597 | Resp. to motor phase failure
Data type: UNSIGNED_8
Index: 23978
d
= 5DAA
h
Response to motor phase failure
• If a phase current does not exceed the threshold set in
for more than one period, the response set here
will be triggered.
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00598 | Resp. to I/O monitoring
Data type: UNSIGNED_8
Index: 23977
d
= 5DA9
h
Configuration of monitoring of the analog inputs
Selection list
0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
5 Warning
Subcodes
Lenze setting
Info
C00598/1
3: TroubleQuickStop
Response to open circuit at AIN1 if configured as
4 ... 20 mA current loop
C00598/2
3: TroubleQuickStop
Response to open circuit at AIN2 when being configured
as 4 ... 20 mA-current loop
C00598/3
5: Warning
Resp. to digital output level
C00598/4
5: Warning
Resp. to IO supply overload
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00599 | Motor phase failure threshold
Data type: INTEGER_16
Index: 23976
d
= 5DA8
h
Threshold for motor phase failure monitoring
• 100 % ≡ rated inverter current (
• If a phase current does not exceed the threshold set here for more than one period, the response to motor phase
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
100.00 5.00 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100