C01903 | diagnostics x70: change baud rate, C01905 | diagnostics x70: current baud rate, C02200 | ls_writeparamlist: function – Lenze 8400 User Manual
Page 1021: C02200/1, C02200/2, 16 parameter reference

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
1021
16
Parameter reference
16.2
Parameter list | C01903
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01903
C01905
C02200
Parameter | Name:
C01903 | Diagnostics X70: Change baud rate
Data type: UNSIGNED_8
Index: 22672
d
= 5890
h
New baud rate determination at the diagnostic interface X70
Selection list
(Lenze setting printed in bold)
0 Ignore changes
1 Negotiate baud rate
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C01905 | Diagnostics X70: Current baud rate
Data type: UNSIGNED_32
Index: 22670
d
= 588E
h
Current baud rate at the diagnostic interface X70
Display range
(min. value | unit | max. value)
0
Bd
3000000
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C02200 | LS_WriteParamList: Function
Data type: UNSIGNED_8
Index: 22375
d
= 5767
h
From version 12.00.00
Configuration of which parameter lists are to be subject to the "
" function.
Selection list
0 Off
1 On
Subcodes
Lenze setting
Info
C02200/1
1: On
Definable parameter list
C02200/2
0: Off
Motor data parameter list
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1