68 l_curve_2, 68 l_curve_2 5, L_curve_2 – Lenze 8400 User Manual
Page 1245: 18 function library

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
1245
18
Function library
18.1
Function blocks | L_Curve_2
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
18.1.68
L_Curve_2
This FB can optionally display a characteristic function or a curve function y=f(x), the X axis being
the input signal and the Y axis being the output signal.
• A limitation of the input value can be set in
(upper limit) and
(lower limit).
• The output value is internally limited to ±199.99 %. If a limitation of the output value is active,
bLimit is set to TRUE.
Inputs
Outputs
Parameter
Identifier
Data type
Information/possible settings
nIn_a
INT
Input value (x)
• ±16384 ≡ ±100 %
• A limitation of the input value can be set in C01026/1 (upper limit) and C01026/2
(lower limit).
Identifier
Data type
Value/meaning
nOut_a
INT
Output value (y)
• ±16384 ≡ ±100 %
• Internal limitation to ±32767 (±199.99 %)
bLimit
BOOL
"Limitation active" status signal
TRUE The output value is limited to ±199.99 %.
Parameter
Possible settings
Info
-199.99
%
199.99 Output value
• Read only
Function selection
0 nOut_a = 0 (FB deactivated)
Lenze setting
1 nOut_a = nIn_a
2 nOut_a = f(x)
In preparation!
3 nOut_a = f(table)
See description of L_Curve_1:
-199.99
%
199.99 Upper limit for input value
• Lenze setting: 199.99 %
-199.99
%
199.99 Lower limit for input value
• Lenze setting: -199.99 %
/B&XUYHB
Q2XWBD
Q,QBD
E/LPLW
& )XQFWLRQ
[
\
[
\
&
&
&[
&[
&
;9DOB
<9DOB