Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
775
16
Parameter reference
16.2
Parameter list | C00155
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00155
Parameter | Name:
C00155 | Extended status word
Data type: UNSIGNED_16
Index: 24420
d
= 5F64
h
Bit coded device status word 2
Display area
(min. hex value | max. hex value)
0x0000
0xFFFF
Value is bit-coded:
Info
Bit 0 Fail
Fault
Bit 1 M_max
Maximum torque
Bit 2 I_max
Maximum current
Bit 3 PowerDisabled
Power switched off
Bit 4 Ready
Controller is ready for operation
Bit 5 ControllerInhibit
Controller is inhibited
Bit 6 Trouble
Trouble
Bit 7 InitState
Initialisation
Bit 8 CwCcw
CW/CCW rotation
Bit 9 TroubleQSP
Quick stop due to fault is active
Bit 10 SafeTorqueOff
Safe torque off
Bit 11 AplicationRunning
Application is running
Bit 12 AplParSetBit0
Application parameter set - bit 0
Bit 13 AplParSetBit1
Application parameter set - bit 1
Bit 14 Quick stop
Quick stop active
Bit 15 Motor parameter identification
Motor parameter identification is active
Read access Write access CINH PLC STOP No transfer COM MOT